11030GEVD404
New product
A line of power and control panels for refrigeration systems with three-phase compressor up to 4 HP, for the complete management of cold room. Magnetothermic protection and motor circuit breaker for the compressor accessible from the front panel linked to an innovative form makes it a perfect and functional choice. Integrated GSM module that sends an alarm phone call.
This product is no longer in stock
Warning: Last items in stock!
Availability date:
Main Function | Full cold room management |
User interface | Red Led big (Base/Expert series) |
Datalogger | No |
General protection | Magnetothermic |
Compressor - type | Three phase |
Compressor - thermal protection | 2.2 - 3.2 A |
Product type | Electrical panel with electronics |
Condenser - type of fans | Single phase |
Condenser - Total fan power | up to 800 W |
Condenser - separated fans | No |
Evaporator- fans phases | Single phase |
Evaporator - fans power | 500 W |
Defrost - type | With heaters / off-cycle |
Defrost - heaters phases | Three phase |
Defrost - heaters power | 6000 W |
Light - power | 800 W (AC1) |
Other characteristics | Pump-down / Thermostat (PD/T), Door switch, Compressor oil heater, Integrated GSM module |
• Direct control of the compressor, condenser fans, compressor oil heater, defrosting heaters, evaporator fans, solenoid valve, room light and all standard-compliant electrical safeguards.
• General magnetothermic circuit breaker accessible from the front panel, which cuts the general power supply.
• Adjustable motor circuit breaker for compressor protection accessible from the front panel.
• Easy wiring on the internal terminal block.
• Selection of functioning mode for the compressor (pump-down / thermostat).
• Auxiliary relay with activation configurable by parameter.
• Transparent cover for access to magnetothermic circuit breaker, all with IP 65 protection rating.
• Electronic control with wide LED display and easy to use buttons.
• Signaling with LED icons of the plant status.
• RS485 for connection to TeleNET industrial supervision network or modbus-RTU standard protocol.
• Integrated EXPERT GSM module: it sends an alarm phone call to report the anomaly of the cold room.